FrostyGoop: Modbus Attack on OT Heating Controls
A district-heating utility's internet-facing edge appliance was compromised via default credentials, giving an attacker access to the IT/historian segment. From there they deployed a purpose-built Modbus TCP tool to overwrite operating setpoints on three ENCO district-heating controllers, cutting off heat to hundreds of downstream customers in the middle of winter. Reconstruct the intrusion chain from SIEM (Windows/Sysmon + SCADA alarms), PCAP (Modbus write transactions), and firewall logs.
Start this operation
Investigation Tasks
Complete each task by investigating alerts and submitting your findings.
Locate the initial foothold
35The plant lost heat overnight. Before anything else, establish where the attacker's first successful access point was and how they got in.
Trace the pivot into the OT historian
40The attacker did not stay at the edge. They moved inward to a more sensitive host before deploying their tooling. Identify the internal host they reached and the technique used to get there.
Identify the ICS tool used to write the controllers
45Once inside the historian, the attacker staged a purpose-built ICS tool before attacking the controllers. Name the binary that was dropped and executed.
Decode the Modbus function code used for the attack
40The PCAP captures the actual Modbus TCP transactions between the historian and the ENCO controllers. The attack does not use the same function code as the normal scheduled reads. Identify the Modbus function code used to modify the controller registers.
Identify the impacted register that controls operating mode
45FrostyGoop wrote to two specific Holding Registers on each controller. One controls the supply-temperature setpoint; the other controls the operating mode of the heating circuit. Identify the register address for the operating-mode control.
Map the attack to its ATT&CK for ICS technique
40The core of this intrusion is the deliberate manipulation of controller parameters to disrupt a physical process. Map the Modbus register-write campaign to its MITRE ATT&CK for ICS technique ID.
Establish the physical impact
35The register writes translated into a real-world physical consequence. The SCADA alarm log tells you what the plant actually experienced. Identify how many distinct heating circuits were taken offline by the attack.
Identify the firewall rule gap that enabled the attack
35The attack succeeded partly because a firewall rule at the IT/OT boundary permitted sessions that should never have been allowed. Identify the name of the rule that allowed the historian to initiate Modbus write connections to the controllers.
Attribute the initial access technique
35The very first step of this intrusion exploited a specific configuration weakness in how the organization exposed its operational technology environment to the internet. Identify the ATT&CK for ICS technique that describes adversaries gaining access through internet-accessible industrial devices or management interfaces.
9 tasks · 350 points total
Training Tools
Skills You'll Build
Complex multi-stage investigations. Realistic noise, ambiguous indicators, lateral movement.
Prerequisites
- Basic understanding of security alerts
- Experience with log analysis tools
- Familiarity with SIEM concepts
- Familiarity with Firewall concepts
Ready to investigate?
More Operations
View allDPRK Fake IT Worker: Insider Access and Exfiltration
A fraudulent remote software engineer embedded under a stolen identity gains network access on their first day and immediately begins collecting source code, architecture documentation and cloud secrets. The session originates entirely from a single hosting-range ASN, persists through AnyDesk and ngrok tunnels, and ends with a dual-channel exfiltration via Rclone and AzCopy. Reconstruct the full chain from Azure AD audit events, VPN and endpoint telemetry.
UNC3886: vCenter RCE to ESXi Persistence (CVE-2023-34048)
Orbivex Aerospace runs its virtualisation estate on a vCenter Server appliance and three ESXi hypervisors, with the vCenter HTTPS management interface published to the internet. The platform team opened a ticket during the morning shift: the appliance had logged a management daemon terminating on a fatal signal and restarting, and the hypervisor integrity summary listed package and startup-file entries the change record does not account for. Work the vCenter, ESXi and firewall telemetry and establish what reached the estate, how it moved between the management plane and the hypervisors, and how far it got.
FIN7 Carbanak: Spear-Phish to Backdoor Intrusion
A macro-enabled Word attachment reached an accounting workstation at Valdoria Hotels Group. Within minutes the POWERTRASH backdoor was loaded, injected into a Windows system process, and beaconing to external infrastructure. Days of patient reconnaissance followed before the operator reached the financial server and deployed a custom tool against the SWIFT transaction interface. Reconstruct the full intrusion chain across endpoint, network, and perimeter telemetry.